የፊት ገጽ > የምርት ማዕከል > 35-220KV Power Substation Equipment > SF6 Circuit Breaker > ZCW 72.5 126.5 L Open Air Type High Voltage Assembled Switchgear 72.5kV Gas Insulated Circuit Breaker Outdoor AIS Switchgear for Substation

ZCW 72.5 126.5 L Open Air Type High Voltage Assembled Switchgear 72.5kV Gas Insulated Circuit Breaker Outdoor AIS Switchgear for Substation

    ZCW 72.5 126.5 L Open Air Type High Voltage Assembled Switchgear 72.5kV Gas Insulated Circuit Breaker Outdoor AIS Switchgear for Substation

    The ZCW 72.5 126.5 L Open Air Type High Voltage Assembled Switchgear combines 72.5kV gas-insulated circuit breaker technology with robust outdoor AIS design, providing reliable, durable, and high-performance electrical protection for substations. Ideal for efficient power distribution, fault management, and outdoor high-voltage applications, it ensures safe and stable operation under demanding conditions.
  • አጋራ:
  • አግኙን የመስመር ላይ ጥያቄ
  • ደብዳቤ:sales@vcbbreaker.com
    WhatsApp:8613736779975

Structural Features

The circuit breaker, disconnecting switch, grounding switch, current transformer, busbar, and other components are organically combined on a grounded steel frame, resulting in a compact structure. It occupies only 30%-50% of the space compared to a separate-type configuration, offering significant advantages such as land savings and reduced construction costs.


The entire compartment is prefabricated in the factory, with assembly and all commissioning completed before shipment, allowing for transportation as a complete unit to the installation site. This greatly shortens the installation period. The design utilizes highly proven, high-performance arc-extinguishing chambers and disconnecting switches, which require minimal maintenance and have high reliability.


The self-supporting busbar, prefabricated in the factory, eliminates the need for the user to build a frame. The layout is flexible and can accommodate various wiring configurations. The circuit breaker can be fully lowered for maintenance or replacement. In the event of a failure, the downtime can be reduced to less than 3 hours, minimizing power outages.

Main Technical Parameters of Circuit Breaker

No.NameUnitParameter
1Rated voltagekV72.5
2Rated power frequency withstand voltage (1 Minute) – GroundedkV160

Rated power frequency withstand voltage (1 Minute) – Contact gapkV200
3Rated lightning impulse withstand voltage – GroundedkV350

Rated lightning impulse withstand voltage – Contact gapkV410
4Power frequency withstand voltage of SF6 gas at zero gauge pressure (5 min)kV84
5Rated frequencyHz50
6Rated currentA3150
7First level coefficient
1.5
8Rated short-circuit breaking currentkA31.5
9Rated short-circuit making current (peak value)kA80
10Rated short-circuit withstand currentkA31.5
11Rated peak withstand currentkA80
12Rated short circuit durations4
13Rated out of step breaking currentkA8
14Short-range fault breaking currentkA90%Ik, 75%Ik
15Rated line charging switching currentA10
16Rated operating sequence
0-0.3s-CO-180s-CO
17Main circuit resistanceµΩ≤ 40
18Rated sulfur hexafluoride gas pressure (20°C gauge pressure)MPa0.5
19Alarm/minimum function pressure (20°C gauge pressure)MPa0.45±0.03
20SF6 gas annual leakage rate
<0.5%
21Gas moisture content (V/V)
≤150×10⁻⁶
22Mechanical lifeTimes10000
23Radio interference levelµV≤500
24Creep distance – Contact gapmm2585

Creep distance – Groundedmm2248
25Weight of each unit filled with SF6 gaskg10
26Weight of each circuit breakerkg1300