LN2-40.5 Indoor SF6 Circuit Breaker High Voltage Reliable Durable Electrical Protection for Switchgear Substation

    LN2-40.5 Indoor SF6 Circuit Breaker High Voltage Reliable Durable Electrical Protection for Switchgear Substation

    The LN2-40.5 Indoor SF6 Circuit Breaker offers high voltage electrical protection for switchgear and substations. Designed for reliability and durability, it ensures efficient circuit interruption under high stress. With SF6 gas insulation, it maintains excellent performance in demanding environments, providing safe and stable electrical protection for critical infrastructure.
  • አጋራ:
  • አግኙን የመስመር ላይ ጥያቄ
  • ደብዳቤ:sales@vcbbreaker.com
    WhatsApp:8613736779975

The LN2-40.5 indoor SF6 circuit breaker is an indoor device designed for use in 50 Hz three-phase AC systems. It is suitable for industrial enterprises, power plants, and substations for protection and control purposes and can be used in locations requiring frequent operations. It can also be used as a link circuit breaker and for switching capacitor banks.

The LN2-40.5 model is equipped with the CT10-A spring operating mechanism but can also be paired with the CD101G electromagnetic operating mechanism.

Main Technical Parameters of Circuit Breaker

(Model: LN2-40.5/1250A-25)

No.Parameter NameUnitParameter Value
1Rated voltagekV40.5
2Maximum working voltagekV40.5
3Rated insulation levelkV185 (lightning impulse, full wave) /
95 (power frequency, 1 min)
4Rated frequencyHz50
5Rated currentA1250
6Rated short-circuit breaking currentkA25
7Rated operating sequenceO—0.35s—CO—180s—CO*
8Rated short-circuit making current (peak)kA63
9Rated dynamic stability current (peak)kA63
10Rated thermal stability currentkA25
11Rated thermal stability durations4
12Switching current for a single capacitor bankA400
13Rated out-of-step breaking currentkA6.3
14Accumulated breaking times (rated current)Times2000
15Accumulated breaking times (rated short-circuit)Times16
16Mechanical life

– With CT10-A spring mechanismTimes6000
– With CD10IIG electromagnetic mechanismTimes5000
17Closing time

– Spring mechanisms≤0.15
– Electromagnetic mechanisms≤0.2
18Inherent opening time (rated voltage)

– Minimum operating voltages≤0.10
– Maximum operating voltages≤0.07
19SF6 gas rated pressure (20℃ gauge)MPa0.65
20SF6 gas alarm pressure (20℃ gauge)MPa0.42
21SF6 gas lock pressure (20℃ gauge)MPa0.4
22SF6 gas annual leakage rate%/Year≤1
23SF6 gas moisture contentppm (V/V)≤150
24Rated operating voltage (CT10-A spring mechanism)

– Closing coilV (DC)48, 110, 220
– Opening coilV (DC)48, 110, 220
– MotorV (DC)110, 220
25Rated operating voltage (CD10IIG electromagnetic mechanism)

– Closing coilV (DC)110, 220
– Opening coilV (DC)48, 110, 220
26Weight

– Circuit breaker bodykg135
– SF6 gaskg1.5


የመስመር ላይ መልእክት

እባክህ የሚሰራ የኢሜይል አድራሻ አስገባ
የማረጋገጫ የሚስጥር ቁጥር ባዶ መሆን አይቻልም

ተዛማጅ ምርቶች

እስካሁን ምንም የፍለጋ ውጤቶች የሉም!
Contact Us

Phone: +8613736779975

E-mail: sales@vcbbreaker.com

Address: 66 Punan Road, Yueqing Economic Development Zone, Zhejiang, China

የቅጂ መብት © 2025 ያንግሪ ኤሌክትሪክ ቡድን ሁሉም መብቶች የተጠበቁ ናቸው

የጣቢያ ካርታ

ይህ ድህረ ገጽ በድረ-ገጻችን ላይ ምርጡን ተሞክሮ እንድታገኝ ኩኪዎችን ይጠቀማል።

ተቀበል አለመቀበል